TENNESSEE EQUIPMENT MODERATED NEWSGROUP AND LIST   >   Midwest   >   Ohio   >   Intec cut out capillary thermostat low limit

Intec cut out capillary thermostat low limit


Control and monitor frost temperature of make-up air heater coils.
• Auto & manual reset • Low temperature
• Six to twenty feet capillary setpoint safety lock
Type of operation On/Off, single-stage, micro switch
Output 1 SPDT, or 2 SPDT, 24 to 250 VAC, 15 (8) A
Differential switching 1.8°F (1°K), fixed for auto reset
Control range 14°F to 54°F (-10°C to 12°C)
Setpoint safety lock At 35.6°F (2°C) factory set, field adjustable
Setpoint adjustment Screw driver slot
Sensing element Vapor-filled copper capillary
Capillary size Diameter 0.08 in. (2 mm)
Permissible ambient temperature
- Capillary, max. 392°F (200°C) max. 60 min.
- Storage, max. -4°F to 158°F (-20°C to 70°C)
Wire - Connection Terminal with wire retaining screws
- Size Maximum 14 AWG (2.5 mm2)
Cable entry M20 fitting, replaceable by 1/2" conduit connection
Housing - Material Metal base, galvanized, ABS cover, fire retardant
- Dimensions 4.1 x 3.3 x 2.1 in. (105 x 83 x 53 mm)
Installation Duct and across coil mounted



Intec cut out capillary thermostat low limit